Pulser wires are required to be in separate conduit than AC power wires by the NEC & local fire code.
-
The shield of the pulser wire should be connected to earth on one end only.
-
Do not earth wires through DC GND on FuelCloud hardware.
-
Keep pulser wires at least 1” away from AC power wires inside FuelCloud equipment.
-
We don't recommend using inline pulsers that are connected on fuel hoses that can be vibrated by the pump. That movement can be read as volume flow.