Pulser Wiring Best Practices

  • Pulser wires are required to be in separate conduit than AC power wires by the NEC & local fire code.

  • The shield of the pulser wire should be connected to earth on one end only.

  • Do not earth wires through DC GND on FuelCloud hardware.

  • Keep pulser wires at least 1” away from AC power wires inside FuelCloud equipment.

  • We don't recommend using inline pulsers that are connected on fuel hoses that can be vibrated by the pump. That movement can be read as volume flow.

  • 2 Wire: Belden 8762
  • 3 Wire: Belden 8772